The existing R22 and R407C piping can be reused for
our digital inverter R410A product installations.
WARNING
Confirming the existence of scratches or dents on
the existing pipes and confirming the reliability of
the pipe strength are conventionally referred to the
local site.
If the specified conditions can be cleared, it is
possible to update existing R22 and R407C pipes
to those for R410A models.
Basic conditions needed to reuse existing
pipes
Check and observe the presence of three conditions in
the refrigerant piping works.
1. Dry (There is no moisture inside of the pipes.)
2. Clean (There is no dust inside of the pipes.)
3. Tight (There are no refrigerant leaks.)
Restrictions for use of existing pipes
In the following cases, the existing pipes should
not be reused as they are. Clean the existing pipes
or exchange them with new pipes.
1. When a scratch or dent is heavy, be sure to use new
pipes for the refrigerant piping works.
2. When the existing pipe thickness is thinner than the
specified “Pipe diameter and thickness,” be sure to
use new pipes for the refrigerant piping works.
The operating pressure of R410A is high (1.6
times that of R22 and R407C). If there is a scratch
or dent on the pipe or a thinner pipe is used, the
pressure strength may be inadequate, which may
cause the pipe to break in the
worst case.
* Pipe diameter and thickness (mm)
In case the pipe diameter is Ø12.7 mm or less and
the thickness is less than 0.7 mm, be sure to use
new pipes for the refrigerant piping works.
3. When the outdoor unit was left with the pipes
disconnected, or the gas leaked from the pipes and
the pipes were not repaired and refilled.
There is the possibility of rain water or air,
including moisture, entering the pipe.
4. When refrigerant cannot be recovered using a
refrigerant recovery unit.
There is the possibility that a large quantity of dirty
oil or moisture remains inside the pipes
.
5. When a commercially available dryer is attached to
the existing pipes.
There is the possibility that copper green rust has
been generated.
6. When the existing air conditioner is removed after
refrigerant has been recovered.
Check if the oil is judged to be clearly different from
normal oil.
The refrigerator oil is copper rust green in color:
There is the possibility that moisture has mixed
with the oil and rust has been generated inside the
pipe.
There is discolored oil, a large quantity of residue,
or a bad smell.
A large quantity of shiny metal dust or other wear
residue can be se
en in the refrigerant oil.
7. When the air conditioner has a history of the
compressor failing and being replaced.
When discolored oil, a large quantity of residue,
shiny metal dust, or other wear residue or mixture
of foreign matter is observed, trouble will occur.
8. When temporary installation and removal of the air
conditioner are repeated such as when leased etc.
9. If the type of refrigerator oil of the existing air
conditioner is other than the following oil (Mineral
oil), Suniso, Freol-S, MS (Synthetic oil), alkyl
benzene (HAB, Barrel-freeze), ester series, PVE
only of ether series.
The winding-insulation of the compres
sor may
deteriorate.
NOTE
The above descriptions are results have been confirmed
by our company and represent our views on our air
conditioners, but do not guarantee the use of the existing
pipes of air conditioners that have adopted R410A in
other companies.
Curing of pipes
When removing and opening the indoor or outdoor unit
for a long time, cure the pipes as follows:
Otherwise rust may be generated when moisture or
foreign matter due to condensation enters the pipes.
The rust cannot be removed by cleaning, and new
pipes are necessary.
Pipe outer diameter Ø6.4 Ø9.5 Ø12.7 Ø15.9 Ø19.0
Thickness
R410A
0.8 0.8 0.8 1.0 1.0
R22
(R407C)
Placement
location
Term Curing manner
Outdoors
1 month or more Pinching
Less than 1 month
Pinching or taping
Indoors Every time
Are there scratches or dents on the existing pipes?
Piping necessary to change the flare nut / machining
size due to pipe compression
1) Flare nut width: H
2) Flare machining size: A
Do not apply refrigerator oil to the flare surface.
(mm)
Copper
pipe outer
diameter
Ø6.4 Ø9.5 Ø12.7 Ø15.9 Ø19.0
For
R410A
17 22 26 29 36
For R22
Same as
above
24 27
Same
as
above
H
(mm)
Copper
pipe outer
diameter
Ø6.4 Ø9.5 Ø12.7 Ø15.9 Ø19.0
For
R410A
9.1 13.2 16.6 19.7 24.0
For R22 9.0 13.0 16.2 19.4 23.3
Becomes a little larger for R410A
A
YES
NO
YES
NO
YES
NO
Is it possible to operate the existing air conditioner?
After the existing air conditioner is operated in
cooling mode for approx. 30 minutes or longer,*
recover the refrigerant.
For cleaning the pipes and recovering oil
Refrigerant recovery: Pump down method
Remove the existing air conditioner from the piping
and carry out flushing (nitrogen pressure 0.5 MPa)
to remove any remains inside of the pipe.
Note: In case of twin pipes, also be sure to flush the
branching pipe.
Was largely discolored oil or a large quantity of
remains discharged? (When the oil
deteriorates, the color of the oil changes to a
muddy or black color.)
Nitrogen gas pressure 0.5 MPa
Existing pipes: Cannot be used.
Use new pipes.
Clean the pipes or use new pipes.
(If there is discharge of remains, it is judged that a
large quantity of remains are present.)
Connect the indoor / outdoor units to the existing pipe.
Use a flare nut attached to the main unit for the
indoor / outdoor units. (Do not use the flare nut of the
existing pipe.)
Re-machine the flare machining size to size for
R410A.
In case that a gas pipe Ø19 mm or bigger is used for
the outdoor unit of SM80 (3 HP): (Our R410A model 3
to 6 HP gas pipe size is Ø15.9 mm)
See page 14 “Existing piping”.
(Airtight test), Vacuum dry, Refrigerant charge, Gas
leak check
Test run
1115150101_EN.indd 401115150101_EN.indd 40 8/24/13 9:40 AM8/24/13 9:40 AM